Data Center OutreachNewsDesksDirectoryValvesValve specs
Pratt Industrial, a Mueller brand. Butterfly valves for data center chilled water systems
Home / Valves
Selection

Butterfly Valve Cv Explained: What It Means and How to Use It

Cv tells you how much water a valve passes for a given pressure drop. Here is the formula, a worked example and what to ask the manufacturer for.

What Cv is

Cv is the flow, in gallons per minute of water at about 60 degrees Fahrenheit, that produces a one psi pressure drop across a valve. A higher Cv means the valve passes more flow for the same drop.

The formula

Pressure drop in psi equals the specific gravity times the square of flow divided by Cv. For water, specific gravity is about one. So pressure drop equals flow divided by Cv, all squared.

A worked example

Take a line carrying 1,000 gpm of water through a valve with a fully open Cv of 2,000. Flow divided by Cv is 0.5. Squared, that is 0.25 psi of pressure drop. The valve is not a meaningful loss in that line.

Cv changes with opening

Cv is highest when the valve is fully open and falls as it closes. Manufacturers publish a table of Cv by disc angle. If a valve will throttle, use the Cv at the operating angle, not the fully open number.

What to request

Ask for Cv by size and by opening, and state the test fluid and conditions. The valve kit page has a Cv chart by size for the Pratt Industrial series.

Need the data or a price?
Copy the guide spec, basis of design and schedule rows, or ask for pricing and stock on butterfly valves for chillers, condenser water, liquid cooling and critical facilities.