SelectionCv tells you how much water a valve passes for a given pressure drop. Here is the formula, a worked example and what to ask the manufacturer for.
Cv is the flow, in gallons per minute of water at about 60 degrees Fahrenheit, that produces a one psi pressure drop across a valve. A higher Cv means the valve passes more flow for the same drop.
Pressure drop in psi equals the specific gravity times the square of flow divided by Cv. For water, specific gravity is about one. So pressure drop equals flow divided by Cv, all squared.
Take a line carrying 1,000 gpm of water through a valve with a fully open Cv of 2,000. Flow divided by Cv is 0.5. Squared, that is 0.25 psi of pressure drop. The valve is not a meaningful loss in that line.
Cv is highest when the valve is fully open and falls as it closes. Manufacturers publish a table of Cv by disc angle. If a valve will throttle, use the Cv at the operating angle, not the fully open number.
Ask for Cv by size and by opening, and state the test fluid and conditions. The valve kit page has a Cv chart by size for the Pratt Industrial series.