What matters when specifying butterfly valves on condenser water loops: water quality, materials, isolation points and how the loop differs from chilled water.
Condenser water leaves the chillers warm, runs to the cooling towers and returns cooler. Unlike chilled water it is often an open loop, which means oxygen, dirt, biological growth and treatment chemicals all reach the valves. Valve materials and coatings that are fine on a closed chilled water loop can wear faster here.
Isolate each chiller condenser, each cooling tower cell, each condenser water pump and the heat rejection header. A plant that can take one tower cell or one pump out of service without shutting down the others is a plant that can be maintained during live operation. Count the valves per cell and per pump in the drawings, because this is where valve counts add up quickly.
Ask what the water treatment program is, and name disc, stem and seat materials with that in mind. Stainless steel discs and stems are a common upgrade in open loops. Resilient seats should be chosen for the temperature and chemicals present, and the rating on the cut sheet should be checked against the maximum condenser water temperature for the plant.
Most condenser water piping fits the BF and OS series at 150 to 250 psi class ratings. The OS series covers 1 to 48 inch at 200 psi up to 12 inch and 150 psi above, and the BF series covers 2 to 24 inch with ratings of 250 psi up to 12 inch and 150 psi from 14 inch. Use the line size checker on the valve kit page to confirm any size.
Towers in cold climates run with low flow and low temperature. Make sure any throttling or bypass valve is sized so it is not operating almost closed at low load, since butterfly valves throttle best in the middle of their travel.
Write the valve in the spec as a resilient seated butterfly valve per API 609 Category A, bubble tight shutoff, tested to API 598, with the materials stated for the water treatment. The guide spec on the valve kit page includes that language.