Valves for Liquid Cooling and CDU Loops in AI Data Centers

Where isolation valves go on facility water and technology cooling loops feeding coolant distribution units, and what to ask for when specifying them.

Two loops, two jobs

Direct to chip liquid cooling usually runs two water loops. The facility water loop moves heat from the coolant distribution units (CDUs) to the chillers or dry coolers. The technology cooling loop carries coolant from the CDU to the cold plates on the servers. Large butterfly valves live mainly on the facility side, the primary side of the CDU, where pipe sizes are big and flow rates are high.

Why isolation matters more now

AI racks put much more heat in each cabinet, so a loop outage affects more compute for the same footprint. Being able to isolate one CDU, one pump or one branch without touching the rest of the loop is a core design goal. That means more isolation points, installed where service access is good, and valves that seal bubble tight so they can actually be trusted for maintenance.

Glycol and stainless steel

Many liquid cooling loops use water and glycol mixtures and tight water quality limits. Stainless steel body, disc and stem options reduce corrosion and particulate risk. Check that seat materials are compatible with the glycol type and the maximum temperature, and ask for the compatibility statement in the submittal.

Series and sizes

Branch and CDU connections often fall in the 2 to 12 inch range, which the BF and OS series cover, with header and plant piping going larger. Where pressure is higher, HP series double offset valves cover Class 150, 300 and 600 ratings. The pressure gauges on the valve kit page show every rating at a glance.

Actuation and monitoring

For critical loops, valves are often fitted with actuators and position feedback so the control system knows if a valve is open or closed. Specify the actuator type, the fail position and the limit switches in the spec, and decide who coordinates between the valve supplier and the controls contractor.

What owners ask for

Owners with an approved manufacturer list will want the valve to be on it before the bid. Getting a valve onto that list takes time, so the article on approved manufacturer lists explains how it works and what information to collect.