Data centers · Chillers · Condenser water · Liquid cooling · Critical facilities
Valve data you can paste straight into your plans
Pratt Industrial butterfly valves, laid out for the people drawing and specifying the job. Sizes, pressures, materials, Cv, model strings, a Division 23 guide spec and a basis of design paragraph. One click copies each one. Nothing to sign up for.
Almost every butterfly valve on a cooling loop is one of two designs. Resilient seated valves (BF and OS) seat into an elastomer ring. High performance double offset valves (HP) seat into a fluoropolymer seat set back behind the shaft. Start with the flange class and size of the line.
Series
Design
Sizes
Pressure
Body
Good fit for
BF
Resilient seated, wafer or lug
2"–24"
250 psi (2"–12"), 150 psi (14"–24")
Ductile iron
Chilled water and condenser water isolation at ANSI 125/150 flanges
OS
Resilient seated, wafer or lug
1"–48"
200 psi (1"–12"), 150 psi (14"–48")
Ductile iron
The widest size range for mechanical rooms and large headers at ANSI 125/150 flanges
HP
High performance double offset
2"–72"
Class 150: 285 psi · Class 300: 740 psi · Class 600: 1440 psi
WCB carbon steel or CF8M stainless
CDU and technology cooling loops, glycol service, higher pressure classes, modulating duty
Pressure at a glance
Every rating on one scale, 0 to 1500 psi. Blue is resilient seated (BF and OS). Orange is high performance (HP). Then check your own line below.
Resilient seated · BF and OS
High performance double offset · HP
Flow capacity by size
Cv at full open for the size you pick. Higher Cv means less pressure drop across the valve.
Cv at full open
Full tables by degree of opening, 10° through 90°, are in each brochure. If a valve will do any control work, size against Cv at the position it will actually sit, not the full open number. A 12" BF at 60° open is 2,799 against 9,245 wide open, roughly 30% of full capacity.
Size
BF
OS
HP Cl 150
HP Cl 300
HP Cl 600
2"
206.4
115
88
88
—
4"
825.6
600
410
410
243
6"
1,858
1,579
1,060
995
630
8"
3,302
3,136
2,200
1,900
1,100
12"
9,245
8,250
4,700
4,100
2,700
16"
16,435
16,388
7,900
6,900
5,100
20"
25,680
27,908
13,800
12,600
7,800
24"
36,979
43,116
21,100
18,900
12,500
Series data, ready to copy
Each card has the facts engineers ask for first. The schedule row pastes as tab separated columns into a Revit valve schedule or a spreadsheet.
BF Series
Resilient seated · wafer BF1 / lug BF2 · API 609 Cat. A
A thin, high-flow disc on a two-piece shaft with full-length bushings. A three-point tongue-and-groove seat holds under high dead-end pressure and full vacuum.
Sizes
2" to 24"
Pressure
250 psi 2"–12" · 150 psi 14"–24"
Body
One piece ductile iron ASTM A536 65-45-12
Disc
Ductile iron with ENP plating or nylon 11, CF8M stainless, or aluminum bronze
Shaft
Heat treated 416 stainless, two shafts, blowout proof
Resilient seated · wafer OS1 / lug OS2 / flanged OS3 · API 609 Cat. A
The same tongue-and-groove seat design as the BF, in the widest size range of the three. Three upper bushings and one lower bushing reduce stem friction and torque.
Double offset · API 609 Cat. B · API 607 fire-safe
A double offset disc with a spherical sealing surface and a free-floating, pressure-assisted seat. Fluoropolymer seat options, higher pressure classes, and sizes up to 72".
Sizes
2" to 72"
Pressure
Class 150: 285 psi (2"–72") · Class 300: 740 psi (2"–48") · Class 600: 1440 psi (3"–24")
Body
WCB (A216) carbon steel or CF8M (A351) stainless. Other alloys on request
Disc
CF8M (A351) stainless
Shaft
Hardened 17-4 PH stainless, one piece, blowout proof
Seat
PTFE, RTFE or MTFE standard, with 316 stainless, Inconel, metal and fire-safe options
Body styles
HP1 wafer · HP2 lug · HP3 short flanged · HP4 long flanged · HP5 butt-weld
Standards
ASME B16.34, API 607, API 598 (100% tested), MSS SP-68, ASME B16.10, ISO 5752, BS 5155
Extras
Gland packing below the bonnet so automation direct mounts, 2" minimum neck clearance for insulation, integral travel stop. Test reports and MTRs on request
Ductile iron and carbon steel are standard. Stainless is available on every series, so say it in the spec when the service calls for it. Stainless parts also change the pressure rating on some builds, so confirm with the manufacturer.
Series
Body
Disc
Stainless options
BF
Ductile iron A536 65-45-12
Ductile iron ENP or nylon 11, CF8M stainless, aluminum bronze
CF8M stainless body and disc, 17-4 PH stainless shaft, 316 stainless or Inconel seat options. Other alloys on request, including Alloy 20, Hastelloy C276, Monel and Duplex 2205
Watch each valve open and close. The first two drawings look down the shaft. Closed, the disc blocks the pipe. Open, it turns to lie along the flow. The last two look down the pipe at the body styles. Product photos for every series are on the manufacturer series pages.
BF and OS
Resilient seated. The disc presses into an elastomer ring (EPDM, Buna-N or Viton) in the body.
HP
Double offset. The shaft sits behind the disc, so the disc lifts away from the seat as it opens, and drags less. PTFE, RTFE, MTFE or metal seat.
Wafer
Sits between two flanges. Lightest and most compact. Not for dead-end service.
Lug
Tapped bolt holes. Each flange bolts to the valve on its own, so it suits dead-end service.
Where the valves go in a cooling plant
A data center is a water plant with servers in it. A butterfly valve on a chilled water loop gets chosen during design, bought during construction, and stays where it is for as long as the building runs. Isolation and control points show up through every loop below. Final locations are always per system design.
Loop
Typical service
What matters
Chilled water, closed
Isolation at chillers, pumps, air handlers and headers. Balancing and control with actuation
Elastomer selection against treatment chemistry. Full vacuum rating
Condenser water, open
Isolation at towers, condensers and pumps. Basin and bypass
Open loop chemistry. Lug body where dead end service is required
CDU and technology cooling
Isolation and control on liquid cooling distribution, water-glycol
Fluoropolymer seat options. Higher pressure classes available
Waterside economizer
Changeover and isolation
Operating pressure and cycling frequency drive the choice
Makeup and facility water
Isolation on makeup, fill and drain
Standard trim per site water quality
What a cut sheet does not tell you
The questions that come up most once a valve is on the drawing.
Disc projection beyond the body face
The disc swings past the face of the valve as it opens. Check the ØA and ØB dimensions against the pipe ID before committing a layout, especially next to a reducer, a fitting or lined pipe.
Weight, for supports and hangers
A 24" BF lug is roughly 408 lbs bare. A 24" HP Class 300 lug is roughly 1,005 lbs and Class 600 roughly 2,110 lbs. Add the actuator on top.
Insulation clearance
HP carries an extended neck with a minimum 2" bonnet to flange clearance on all sizes. On BF and OS, check the E dimension against your insulation thickness.
Actuator mounting
All three series use an ISO 5211 top flange. BF also carries Kv industrial drilling and HP offers ISO drilling on request.
Getting the part number right
If a specific disc or seat material needs to arrive, it has to be in the model string. Each brochure has the ordering table.
Three questions to settle early
1. Which positions modulate rather than isolate. 2. What is the actual fluid, since glycol percentage and water treatment drive elastomer selection and EPDM, Buna-N and Viton are not interchangeable. 3. Where dead end service is required, since a wafer body has no mechanical attachment to either flange and HP vacuum-rated dead end service is lug type only.
Get the valve on the spec before the bid Valves are one of the last things planned on a cooling system. The teams that name a basis of design early avoid the scramble later.
Five steps to a listed manufacturer
Name a basis of designPaste the paragraph from the guide spec into Section 23 05 23 while the mechanical spec is open.
Add to the approved listPut the manufacturer on the owner's approved manufacturer list or master spec so every project inherits it.
Attach the submittal dataCut sheets, Cv tables, dimensional data and suggested spec language are published for every series.
Confirm stock and lead timeAsk before the bid, not after. Use the request template in the stock tab.
Name a local distributorDistributors stock and ship across the country. Ask for the nearest one.
What a company needs for its approved list
Requirements vary by owner and engineer. Most ask for the items below. A manufacturer name and location is enough to start. A person's name and a street address are not required to name a basis of design.
Manufacturer name and location
Product lines and model strings
Design and test standards (API 609, API 598)
Cut sheets and suggested specification language
Cv data by degree of opening
Dimensional data for wafer and lug
Material test reports and test certificates (HP, on request)
Distributor or local contact
Company forms such as insurance, safety and tax, through supplier registration on request
Manufacturer information, ready to paste
MANUFACTURER INFORMATION FOR APPROVED MANUFACTURER LIST
Manufacturer: Pratt Industrial
Location: Emporia, Kansas. Manufacturing, warehouse and full-service machine shop, over 65,000 sq ft
Customer service: 1.800.423.1323
Web: prattindl.com
Products: Butterfly valves. BF Series (2 to 24 in), OS Series (1 to 48 in), HP Series double offset (2 to 72 in)
Pressure: BF 250 psi (2-12 in) and 150 psi (14-24 in). OS 200 psi (1-12 in) and 150 psi (14-48 in). HP Class 150, 300 and 600
Standards: API 609, API 598, ISO 5211, ASME B16.1 / B16.5. HP also ASME B16.34 and API 607
Actuation: Lever, worm gear, pneumatic, electric
Documents available: Cut sheets, suggested specification language, Cv tables, dimensional data, CAD files. Material test reports and test certificates on request (HP)
Submittal package requests: info@datacenteroutreach.com
Where the valves come from
65,000+sq ft of manufacturing and warehouse space in Emporia, Kansas
StockedProduct is stocked and distributed through partners across the country
100%of valves leak tested in the factory at rated pressure per API 598
CustomA full-service machine shop handles custom assemblies and non-standard configurations
Stock changes day to day. Ask for current availability on your sizes and materials.
Ask for stock and lead time in one message
Stock and lead time request
Subject: Stock and lead time request
Project / location:
Series (BF, OS or HP):
Size(s) and quantity:
Flange class / pressure:
Body, disc and seat materials:
Wafer or lug:
Actuator (lever, gear, pneumatic, electric):
Need-by date:
Reply to:
Large sizes and actuated assemblies take more planning. Ask early.
Ask about staged delivery on large jobs.
Ask for the nearest distributor that stocks your series.
Put the full model string on the submittal so the right disc and seat arrive.
Valves get planned last, and it shows
A lot of cooling plants are designed with the chillers, towers and CDUs settled first and the valves left as a line on a submittal. What we hear from the field is that this is where jobs slow down.
Valves are bought after design, so the schedule has no room if the first choice is not available.
The wrong seat material or disc is found at commissioning, when changing it costs the most.
Actuator and top flange details get settled late, so automation waits on the valve.
Large sizes and actuated assemblies take longer than people plan for.
Owner-furnished valves arrive without a spec that tells the contractor which ones.
Glycol percentage and water treatment are not checked against the elastomer until late.
Plan these early
Name the manufacturerBasis of design in the spec, not "or equal" alone.
Pick the designResilient seated or double offset, by pressure and duty.
Check the fluidGlycol percentage and treatment drive the seat material.
Settle the actuatorISO 5211 top flange keeps options open.
Confirm stockAsk for availability before the bid.
These are general observations from the field, not a survey. Valve selection and scheduling are always the responsibility of the engineer of record and the contractor.
The paragraph to paste
Naming a basis of design early keeps the submittal, the schedule and the replacement parts simple. These blocks are written to drop into a project specification. Edit them to fit your project.
Basis of design paragraph
BASIS OF DESIGN: Butterfly valves for chilled water, condenser water and liquid cooling loops shall be Pratt Industrial, Emporia, Kansas. Series BF or OS (wafer or lug) for ANSI 125/150 flanged piping, and Series HP (double offset) for ANSI Class 150, 300 and 600 piping as required by pressure and service. Equivalent products by other manufacturers may be submitted for approval by the Engineer.
Approved manufacturer list line
Manufacturer: Pratt Industrial
Product: Butterfly valves, BF, OS and HP Series
Sizes: 1 to 72 inches
Standards: API 609, API 598, ISO 5211, ASME B16.1 / B16.5
Location: Emporia, Kansas (manufacturing, warehouse and machine shop)
Web: prattindl.com
Customer service: 1.800.423.1323
Division 23 guide spec
SECTION 23 05 23 - BUTTERFLY VALVES FOR HVAC AND CRITICAL COOLING PIPING
PART 1 - GENERAL
1.1 SUMMARY
A. Section includes resilient seated and double offset butterfly valves for chilled water, condenser water, glycol and liquid cooling piping.
1.2 REFERENCES
A. API 609, Butterfly Valves: Double-flanged, Lug- and Wafer-type.
B. API 598, Valve Inspection and Testing.
C. API 607, Fire Test for Quarter-turn Valves (HP Series with fire-safe seat).
D. ASME B16.1 and B16.5, Flanges. ASME B16.34, Valves.
E. ISO 5211, Actuator Attachment. ISO 5752, Face-to-Face Dimensions.
1.3 SUBMITTALS
A. Product data, dimensions, materials of construction, pressure ratings and Cv data.
B. Actuator and accessory data where valves are automated.
1.4 QUALITY ASSURANCE
A. Each valve shall be leak tested in the factory at its rated pressure per API 598.
PART 2 - PRODUCTS
2.1 MANUFACTURER
A. Pratt Industrial, Emporia, Kansas, or approved equal.
2.2 WAFER AND LUG BUTTERFLY VALVES, 1 TO 48 INCHES (BF, OS)
A. Service: Lug valves shall be designed for installation between ANSI 125/150 flanges. Wafer valves shall be designed for installation between ANSI 125/150 flanges [and PN 10 and PN 16 flanges (BF)]. All valves shall be capable of bi-directional, end of line, bubble tight service to rated pressure and shall be rated to full vacuum service. Design standard: API 609 Category A.
B. Pressure rating: [BF: 250 psi 2 to 12 inches, 150 psi 14 to 24 inches] [OS: 200 psi 1 to 12 inches, 150 psi 14 to 48 inches].
C. Body: One piece ductile iron, ASTM A536 Grade 65-45-12, laying length per ISO 5752, flange connection per ASME B16.1/B16.5.
D. Disc: Ductile iron ASTM A536 Grade 65-45-12 with ENP plating [or nylon 11 coating] [CF8M stainless steel (BF)] [304 stainless steel (OS)] [aluminum bronze]. Disc shall accommodate an upper and lower shaft with a thin center profile giving higher Cv values combined with strength.
E. Shaft: [Heat treated 416 stainless steel (BF)] [Heat treated 410 stainless steel (OS)]. Two shafts, upper and lower. The upper shaft shall have positive engagement in the disc through an internal square drive and be retained by the body top cap. Shaft shall be blowout proof per API 609 with a secondary stem journal seal preventing leakage to atmosphere.
F. Seat: [EPDM] [Buna-N] [Viton], field replaceable. Seat shall have three tongues (two on the side walls and one in the center bore) engaging three grooves in the body to prevent seat movement in a radial and axial direction.
G. Shaft seals: Upper shaft seal shall be [self-adjusting V-type (BF)] [self-adjusting O-ring (OS)], suitable for pressure or vacuum service. Bottom end cap shall contain a captive O-ring creating a positive seal against external leakage.
H. Bushings: [Two full length Nylatron bushings, upper and lower (BF)] [Three upper and one lower RTFE bushing (OS)].
I. Top flange: ISO 5211 for direct actuator mounting.
J. Lug style valves shall be suitable for dead-end service.
K. Operators: [Lever] [Worm gear] [Pneumatic actuator] [Electric actuator].
2.3 DOUBLE OFFSET BUTTERFLY VALVES, 2 TO 72 INCHES (HP)
A. Design: Double offset disc and shaft with a spherical sealing surface and a free-floating, pressure-assisted seat retained between the body and a retention ring. Bi-directional sealing with soft seat. API 609 Category B.
B. Pressure class: [ASME Class 150, 285 psi, 2 to 72 inches] [Class 300, 740 psi, 2 to 48 inches] [Class 600, 1440 psi, 3 to 24 inches], suitable for installation between ASME B16.5 flanges.
C. Body: [WCB carbon steel ASTM A216] [CF8M stainless steel ASTM A351]. Styles: [wafer] [lug] [short flanged] [long flanged] [butt-weld].
D. Disc: CF8M stainless steel ASTM A351. Shaft: One piece hardened 17-4 PH stainless steel, blowout proof.
E. Seat: [PTFE] [RTFE] [MTFE] [316 stainless steel] [Inconel] [Fire-safe, tested to API 607].
F. Bearings: Full length upper and lower, 316 stainless steel impregnated with [PTFE] [graphite].
G. Packing: [Multi-layer PTFE cup and cone] [Die-formed graphite for metal seated and fire-safe valves], located below the bonnet for direct mounting of automation.
H. Integrally cast travel stop and extended neck with a minimum 2 inch bonnet to flange clearance for insulation.
I. Vacuum rated dead end and double dead end service: lug type only.
J. Material test reports and test certificates available on request.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install valves with the disc partly open during flange bolting to protect the seat.
B. Use the flange gasket and bolting recommended by the piping specification. Do not install additional gaskets on resilient seated valves.
C. Verify disc swing clearance against the pipe inside diameter, reducers and fittings before installation.
D. Support valves and actuators independently where weight requires.
3.2 FIELD QUALITY CONTROL
A. Operate each valve fully open and closed to verify smooth travel and position indication before system flushing.
B. Leak test with the piping system per Section 23 21 13.
END OF SECTION 23 05 23
Revit, CAD and cut sheets
Brochures and series pages are public on the manufacturer site. CAD files are sent on request so you always get the current version. Revit families are in progress.
CAD drawings
2D and 3D drawings for the series on this page, with dimensions and actuator mounting data.
info@datacenteroutreach.com
Revit families
In progress for BF, OS and HP. Ask to be sent the families when they are released.
info@datacenteroutreach.com
Cut sheets
Brochures with materials, dimensions, Cv tables and suggested specification language, straight from the manufacturer.
Flow, pressure drop, dead-end service or actuator sizing on a live job. Send the line size, flange class and service.
Ask for data, files or a stock check
Tell us what you are working on. We reply by email at info@datacenteroutreach.com.
Copied
BF Resilient seated butterfly valve, wafer (BF1) / lug (BF2) 2"-24" 250 psi (2"-12") / 150 psi (14"-24") Ductile iron A536 65-45-12 EPDM/Buna-N/Viton API 609 Cat A, API 598 ISO 5211 Pratt Industrial
OS Resilient seated butterfly valve, wafer (OS1) / lug (OS2) / flanged (OS3) 1"-48" 200 psi (1"-12") / 150 psi (14"-48") Ductile iron A536 65-45-12 EPDM/Buna-N/Viton API 609 Cat A, API 598 ISO 5211 Pratt Industrial
HP High performance double offset butterfly valve, HP1-HP5 2"-72" Cl150 285 psi / Cl300 740 psi / Cl600 1440 psi WCB A216 or CF8M A351 PTFE/RTFE/MTFE/316 SS/Inconel/fire-safe API 609 Cat B, API 607, API 598 ISO 5211 (ISO drilling on request) Pratt Industrial
Butterfly valves 2 to 24 inches shall be wafer or lug style, bi-directional, end of line, bubble tight to rated pressure and rated to full vacuum, designed to API 609 Category A and leak tested in the factory per API 598. Body one piece ductile iron ASTM A536 65-45-12. Disc ductile iron with ENP plating or nylon 11, CF8M stainless steel, or aluminum bronze. Shaft heat treated 416 stainless steel, two shafts, blowout proof, with secondary stem journal seal. Seat EPDM, Buna-N or Viton, field replaceable, with three tongue and groove connection points. Two full length Nylatron bushings. Pressure rating 250 psi for 2 to 12 inches and 150 psi for 14 to 24 inches. ISO 5211 top flange. Basis of design: Pratt Industrial BF Series.
Butterfly valves 1 to 48 inches shall be wafer, lug or flanged style, bi-directional, end of line, bubble tight to rated pressure and rated to full vacuum, designed to API 609 Category A and leak tested in the factory per API 598. Body one piece ductile iron ASTM A536 65-45-12. Disc ductile iron with ENP plating or nylon, 304 stainless steel, or aluminum bronze. Shaft heat treated 410 stainless steel, two shafts. Seat EPDM, Buna-N or Viton, field replaceable, with three tongue and groove connection points. Three upper and one lower RTFE bushing. Pressure rating 200 psi for 1 to 12 inches and 150 psi for 14 to 48 inches. ISO 5211 top flange. Basis of design: Pratt Industrial OS Series.
Double offset butterfly valves 2 to 72 inches shall have a spherical sealing surface and a free-floating, pressure-assisted seat, designed to API 609 Category B and ASME B16.34, tested 100 percent per API 598, and fire tested to API 607 where fire-safe seats are specified. Body WCB ASTM A216 or CF8M ASTM A351. Disc CF8M stainless steel. Shaft one piece 17-4 PH stainless steel, blowout proof. Seat PTFE, RTFE, MTFE, 316 stainless steel, Inconel or fire-safe. Gland packing below the bonnet, extended neck with 2 inch minimum insulation clearance. Ratings ASME Class 150 (285 psi), Class 300 (740 psi) and Class 600 (1440 psi). Basis of design: Pratt Industrial HP Series.