InstallationHow flange class, facing and bore affect fit, and what to check before ordering.
Check that the valve flange pattern matches the pipe flange class, for example Class 125 or 150. Bolt patterns of different classes can look alike but differ at some sizes.
Resilient seated valves seal on the seat face and generally need flat or raised faces without damaged surfaces. Do not use a gasket unless the manufacturer says so.
Check the inside diameter of the pipe or flange against the disc diameter. Heavy wall pipe, lined pipe and weld neck flanges reduce clearance.
Valves mating to plastic or lined pipe may need special flanges or spacers so the disc swings freely.
Note flange standard and schedule on the valve schedule, so the supplier can check fit at quote time.