Common Butterfly Valve Installation Mistakes and How to Avoid Them

Mistakes that cause leaks, damaged liners and stuck discs, and the checks that prevent them.

Disc open during installation

Install the valve with the disc slightly open so the seat is not crushed when the flange bolts are tightened. Fully closed installation can damage the seat.

Flange bore interference

Weld neck flanges and lined pipe can have a smaller bore than the valve disc needs. Check disc clearance before installing.

Over tightened bolts

Tighten flange bolts evenly, in a star pattern, to the torque in the manufacturer's guide. Uneven tightening distorts the seat and causes leaks.

Wrong orientation or support

Large valves and actuators need support. Check stem orientation so the actuator is not hanging off the pipe without a brace.

Debris and weld slag

Flush the line before cycling valves. Slag and sand cut seats, and a new valve can be ruined before startup.