InstallationHow lug valves are used at the end of a line, why the rating is often lower and what the spec should say.
A valve is in dead end service when it holds pressure on one side with nothing connected downstream. It is common at the end of a header, at a future connection and at equipment you plan to remove.
Lug style valves with threaded bolt holes can hold pressure with a flange removed on one side, if the manufacturer rates them for it. Wafer valves cannot.
The dead end pressure rating is often lower than the full line rating, and it may depend on the size. Read the cut sheet and compare to the design pressure.
On critical lines, many designers add a blind flange downstream even when the valve is rated, as a second barrier.
Mark every dead end valve on the drawings and require a rating that meets or exceeds line pressure.