Electric vs Pneumatic Actuators on Butterfly Valves

How the two actuator types compare for data center cooling plants, including fail position, speed and what the building needs to supply.

Electric actuators

Electric actuators need only power and a control signal. They suit plants without compressed air and give position feedback easily. Fail to last position is standard, and fail open or closed needs a spring return or battery pack.

Pneumatic actuators

Pneumatic actuators are fast and simple, and spring return gives a reliable fail position. They need clean, dry compressed air, which is common in industrial plants and less so in new data centers.

Speed and cycling

Pneumatic units open and close faster. Electric units can be slowed deliberately to avoid water hammer. Match the speed to the line and the surge risk.

Control signal

Decide early whether the valve is on or off or modulating, and what signal the controls contractor will send. Mixing these up at submittal time causes delays.

What to put in the spec

Name the actuator type, fail position, enclosure rating, power supply, signal and position feedback. Say who mounts, wires and commissions it.