ActuationWhat goes into valve torque, why safety factors matter and what information an actuator supplier needs from you.
Valve torque has three main parts: seating torque to break the seat seal, bearing friction on the stem, and hydrodynamic torque from flow pushing on the disc. The highest number usually occurs at the start of opening or the end of closing.
Higher differential pressure raises torque, especially in larger valves. Valve torque tables are published at a stated differential pressure. Use the actual maximum differential for your system, not just the rated pressure of the valve.
Actuator suppliers apply a safety factor to the published torque to cover aging seats, cold starts and supply voltage drop. Follow the supplier's sizing guide rather than picking the next size up by feel.
Valve size, series, differential pressure, fluid, temperature, open and close time, fail position, power supply and control signal. With that, the supplier can size and quote the package.
Say who supplies, mounts and calibrates the actuator, and require an ISO 5211 mounting pad on the valve so actuators fit without custom brackets.