DesignA practical map of the isolation points that let operators maintain a plant without shutting it down.
Isolate supply and return at every chiller, plus the condenser connections when water cooled, so each machine can be removed without affecting the others.
Isolate suction and discharge. Add a check valve on discharge when pumps run in parallel.
Sectionalize headers so a failure or repair affects only a part of the plant. This is where uptime tier designs earn their redundancy.
Provide isolation at every branch feeding a hall, a CDU group or a row, so work can proceed without a plant wide shutdown.
Mark every isolation valve and give each a tag. Valve counts in the schedule should match the drawings.